Product Ranges

Electronic Timers

                           A-Series

                           B-Series

                           Digital Timers

                           H-Series

                           S-Series

Monitoring Devices


Power Supplies


Annunciators

Energy Management System

Tachometers

Time Switch


Hour Meters

Counters

Unik Temp
                          TX7 Series

                           H3TX Series

                           EX-9 Series

_______________________

A Series

Model :A1DE-X
Rated supply voltage 24V to 240V AC & 24V to 220V DC
Operating Voltage Range -10% to +10% of the rated voltage.
Rated Frequency 50/60 Hz ±5%
Setting Accuracy ±10%max. w.r.t full scale ±100mSec
Repeat Accuracy ±1% max. ±100mSec
Recovery Time 100mSec minimum
Rated Frequency of operation 1800 ±5% operations per hour max
Variation due to voltage change ±2%max ±100mSec
Variation due to temp.change ±5%max. ±100mSec
Variation due to frequency change ±2%max. ±100mSec
Ambient temperature Operation:-10° C to +55° C
Storage: -25° C to +80° C
Humidity Max 85% RH @40° C
Service Life 106 operations minimum(under no load)
Electrical Life 105 operations minimum(under full load)
Connections Screw type terminals with self lifting clamps
Dimensions 22.5 X 75 X 102mm (W X H X D)
Power Consumption AC approx. 3VA/1W
DC approx 2W
Insulation Resistance >100M ohms @ 500V DC
Range Selection 3 Sec,30 Sec,3Min,30Min
Dielectric Strength 01)1.5KV AC(rms),50Hz for 1 Minute.(between INPUT TERMINALS & ENCLOSURE)
02)1.5KV AC(rms),50Hz for 1 Minute.(between relay contact terminals & enclosure)
03)1.5KV AC(rms) ,50Hz for 1 Minute.(between INPUT terminals & relay contact terminals) .
04) 2.0 KV AC(rms) 50Hz for 10-30 sec. (Between non-continuous contacts of the relay)
Immunity to Electro static discharge according to IEC61000-4-2 Level 4(AIR 15KV / Contact 8KV)
Immunity against high Frequency electro magnetic fields according to IEC61000-4-3 Level 3(10V / m)
Immunity against fast transients according to IEC61000-4-4 Level 2(Direct 1KV Symmetrical coupling)
Immunity against surges according to IEC61000-4-5 Level 3(2KV Symmetrical coupling)
Allowable Ripple 3% maximum(for DC supply)
Approval CSA (File No: LR 105610)
Radiated Emission & Conducted Emission As per EN55011 Class A Group1
Degree of pollution and over voltage category 3KV / 2
Disengaging value of i/p voltage 20 V
Enclosure(series) A1D series

Next>>

Issue Date:9/08/06