Model :A1DS |
|
| Rated supply voltage | 110/240V |
| Operating Voltage Range | -20% to +10% of the rated voltage. |
| Rated Frequency | 50 Hz ±5% |
| Control Output | Rated for 5A @ 250V AC / 28V DC, resistive load. |
| Setting Accuracy | ±10%max. w.r.t full scale ±100mSec |
| Repeat Accuracy | ±1% max. ±100mSec |
| Recovery Time | 150mSec minimum |
| Rated Frequency of operation | 1800± 5% operations per hour max |
| Variation due to voltage change | ±2%max ±100mSec |
| Variation due to temp.change | ±5%max. ±100mSec |
| Variation due to frequency change | ±2%max. ±100mSec |
| Connections | Screw type terminals with self lifting clamps |
| Dimensions | 22.5 X 75 X 102mm (W X H X D) |
| Power Consumption | AC approx. 15VA/3W(for 240V AC) AC approx. 10VA/2W(for 110V AC) |
| Insulation Resistance | >100M ohms @ 500V DC |
| Range Selection | 6 Sec,60Sec/ Transfer time 40mSec, 100mSec ± 10mSec |
| Dielectric Strength | 01)2.5KV AC,50Hz for 1 Minute.(between current carrying & non-current carrying parts) 02)1.5KV AC,50Hz for 1 Minute.(between contacts & control circuit) 03)1KV AC ,50Hz for 1 Minute.(between non-continuous relay contacts) |
| Time Range | 0.6 Sec to 60 Sec/Transfer time 40msec, 100msec. |
| Ambient temperature | Operation:-10° C to +55° C Storage: -25° C to +80° C |
| Humidity | Max 85% RH @ 400 C |
| Service Life | 106 operations minimum(under no load) |
| Electrical Life | 105 operations minimum(under full load) |
| Enclosure(series) | A1D Series |
ISSUE DATE:For 240V AC - 05/07/01
For 110V AC - 07/02/02