General Specification:  
Rated voltage (Aux. Supply) 85 V to 270 V AC / DC
Rated Frequency (Aux. Supply) 50 / 60 Hz ±5% for AC only
Configuration 3 Phase, 4 Wire
Power consumption < 10 VA
Accuracy  
Voltage,Current,Frequency

±1% of the display value, ± 1 digit

Input Voltage

3 Phase 4 wire (R, Y, B, N).

415 VAC (VL-LTypical)

 

Input Current

Current inputs (AR, AY, AB)

Ib=5 A

Imax=10A


Input Frequency 50 Hz, ±2%
CT Ratio I primary 1 to 6000 A max
I secondary 5A .
Recovery Time

2 Sec

Environmental Specification:  
Ambient Temperature Operation: -100C to + 550 C
Storage: -250C to + 800 C
Humidity Up to 85% RH @ 400 C
Safety:  
Class of Insulation Class II
Insulation resistance >100M ohms @ 500V DC
Dielectric strength a)2.5KV AC, 50HZ for 1 minute. (Between current carrying & non-current carrying parts)
Electrical connection Screw type terminals with self lifting clamps
Dimension 96 x 96 x 112 mm(W x H x D)