Model : M2-24
Function Programmable fault annunciator
Rated supply Voltage 85V to 270V AC/DC
Rated Frequency 50 / 60Hz ± 5%
Power Consumption 20 VA / 4W
No. of Windows 24
Stand by supply 12V DC
Fault input contacts Selectable NO / NC type for each window
Window Colour Red
Window Size 28.0 mm2
Control Output (No. of Relays)

4

Trip Relay(C,NC,NO)

Alarm Relay (C,NC,NO)

AC Fail Relay(C & NO)

Hooter Relay(C & NO)

Contact Rating 1 C/O rated for 5A @ 250 VAC/ 28 VDC resistive load.
Test Facility Available(operational test)
Standard Operation sequence

1.Manual Reset

2. Auto Reset

3. Manual Reset + Repeat Alarm

4. First in First out

Recovery Time 2 Sec minimum.
Ambient Temperature Operation : -100C to +550C
Storage : -250 C to + 800 C
Humidity Max 85% RH@ 40° C
Service Life(under no load) 106 operations minimum
Electrical Life(under full load) 105 operations minimum
Insulation Resistance >100M ohms @ 500V DC
Dielectric Strength 01) 2.5KV AC,50Hz for 1 minute.(Between current carrying and non-current carrying parts)
02) 1.5KV AC, 50Hz for 1 minute.(Between contacts and control circuit)
03) 750V AC, 50 Hz for 1 minute.(Between non-continuous contacts of the relay)
Electrical Connections Screw type terminals with self lifting clamp terminals
Dimensions 291.0 X 186.5X 82.0mm(L X W X D)
Enclosure (series) 'N' series.
Issue Date :04/12/09