Electronic Timers
A-Series
B-Series
Digital Timers
H-Series
S-Series
Monitoring Devices
Power Supplies
Annunciators
Energy Management System
Tachometers
Time Switch
Hour Meters
Counters
Unik Temp
TX7 Series
H3TX Series
EX-9 Series
_______________________
Model : TS 203B |
|
| Function | Digital Daily Time Switch with 4 Programs |
| Rated Supply Voltage | 240V AC |
| Operating Voltage Range | - 20 % to +10% of the rated supply voltage |
| Rated Frequency | 50Hz ± 5% |
| Control Output | 1c/o rated for 16A @ 250V AC/28V DC resistive load |
| Recovery Time | 100msecs minimum |
| Variation due to voltage change | ± 2 sec max |
| Variation due to temp.change | ± 2 sec max |
| Variation due to frequency change | ± 2 sec max |
| Ambient temperature | 0° C to + 50° C(with no icing) |
| Humidity | Max. 85% RH @ 40° C |
| Service Life (under no load) | 106 operations minimum |
| Electrical Life (under full load) | 105 operations minimum |
| Electrical Connections | Screw type terminals with self lifting clamps |
| Dimensions | 130 X 86 X 65mm (L X W X D) |
| Power Consumption | From mains: AC approx.12.5VA (2.5 W) |
| Insulation Resistance | >100M ohms @ 500V DC |
| Time Range | ON Time: 00H 00M to 23H 59M Duration: 00H 01M to 23H 59M |
| Display | 0.39" LCD |
| Dielectric Strength | a) 2.5KV AC,50Hz for 1minute.(Between current carrying and non-current carrying parts) b) 1.5KV AC, 50Hz for 1 minute.(between contacts and control circuit) c) 1 KV AC, 50 Hz for 1minute.(Between non-continuous relay contacts) |
| Number of Programs | 4 programs per day |
| Battery Back up | 1 year minimum |
| Switching Accuracy | ± 2 sec max. |
| Enclosure (Series) | 'K' Series |