Energy Management System

EMS-02
General Specification:  
Rated voltage (Aux. Supply) 85 V to 270 V AC / DC
Rated Frequency (Aux. Supply) 50 / 60 Hz ±5% for AC only
Configuration 3 Phase, 4 Wire
Power consumption < 15VA / 7.5W
Accuracy:


Voltage, Current, Frequency, PF ± 1 % of the display value ± 1 digit
Input Voltage 3 Phase 4 wire (R, Y, B, N)
415 VAC (VL-L Typical)
Input Current

Current inputs (AR, AY, AB)
Ib = 5A
Imax = 10A

Input Frequency 50 Hz, ±2%
CT Ratio I primary 1 to 6000 A max.
I secondary 5A (fixed)
Recovery Time 2 Sec
Environmental Specification:  
Ambient Temperature Operation: -100C to + 550 C
Storage: -250C to + 800 C
Humidity Up to 85% RH @ 400 C
Safety:  
Class of Insulation Class II
Insulation resistance >100M ohms @ 500V DC
Dielectric strength a)2.5KV AC, 50HZ for 1 minute. (Between current carrying & non-current carrying parts)
Electrical connection Screw type terminals with self lifting clamps
Dimension 96 x 96 x 112 mm(W x H x D)