| Model : H1DT-10(CSA) |
| Function |
ON Delay Timer |
| Rated Supply voltage |
24V to 240V AC & 24 V to 220 V DC |
| Operating
Voltage Range |
- 10% to + 10% of rated voltage |
| Rated
Frequency |
50 Hz ± 5% |
| Control
Output |
2 c/o rated for 5A @ 250V AC/28V DC, Resistive load |
| Allowable Ripple (For DC Supply) |
3% maximum |
| Time Range |
1Sec to 10Sec |
| Setting
Accuracy |
± 10% max.w.r.t. Full Scale ±100 msecs |
| Repeat
Accuracy |
± 1% maximum ±100 msecs |
| Recovery
Time |
100 msecs. minimum |
| Rated
Frequency of operation |
1800 ± 5% operations per hour max. |
| Variation
due to voltage change |
±2% max.±100 msecs |
| Variation
due to temp.change |
±5% max.±100 msecs |
| Variation
due to frequency change |
±2% max.±100 msecs |
| Ambient
temperature |
Operating: - 10° C to + 55° C
Storage : - 25° C to + 80° C |
| Humidity |
Max. 85% RH @ 40° C |
| Service
Life |
106 operations minimum(under no load) |
| Electrical
Life |
105 operations minimum(under full load) |
| Connections |
11 pin plug-in-type |
| Dimensions |
48 x 48x 94mm [W x H x D] |
| Power
Consumption |
AC approx 3VA/1W DC Approx.2W |
| Insulation
Resistance |
>100M ohms @ 500V DC |
| Dielectric Strength |
01)1.5KV AC(rms),50Hz for 1minute.(Between INPUT terminal & enclosure)
02) 1.5KV AC(rms), 50Hz for 1 minute.(between relay contact terminals and enclosure)
03) 1.5 KV AC(rms), 50 Hz for 1minute.(Between input terminals & relay contact terminals)
04) 1.0KV AC(rms), 50Hz for 10-30 sec. (Between non-continuous contacts of the relay) |
| Panel
cutout |
45mm X 45mm |
| Enclosure |
H1D Series |
| Approval |
CSA (FILE NO: LR 105610) |