| Model : H3D-CA |
| Operating
Voltage Range |
- 15% to + 10% of rated voltage |
| Rated
Frequency |
50 Hz ± 5% |
| Control
Output |
2 c/o rated for 5A @ 250V AC/28V DC, Resistive load |
| Setting
Accuracy |
± 1% of set time ±50 msecs |
| Repeat
Accuracy |
0.5% of reading ±50 msecs |
| Recovery
Time |
100 msecs. minimum |
| Rated
Frequency of operation |
1800 ± 5% operations per hour max. |
| Variation
due to voltage change |
±1% max.±50 msecs |
| Variation
due to temp.change |
±1% max.±50 msecs |
| Variation
due to frequency change |
±1% max.±50 msecs |
| Ambient
temperature |
Operating: - 10° C to + 55° C
Storage : - 25° C to + 80° C |
| Humidity |
Max. 85% RH @ 40° C |
| Service
Life |
106 operations minimum(under no load) |
| Electrical
Life |
105 operations minimum(under full load) |
| Connections |
Screw type terminals with self lifting clamps |
| Dimensions |
48 x 48x 94mm [W x H x D] |
| Power
Consumption |
AC approx. 15V A / 3W |
| Insulation
Resistance |
>100M ohms @ 500V DC |
| Descriptive Strength |
01)2.5KV AC,50Hz for 1 Minute(between current carrying & non-current carrying parts)
02)1.5KV AC,50Hz for 1 Minute.(between contacts & control circuit)
3)1KV AC,50Hz for 1 Minute.(between non-continuous relay contacts) |
| Panel
cutout |
45mm X 45mm |