| Model : H1DT-30(CSA) |
| Function |
ON Delay Timer |
| Rated Supply Voltage |
24 V to 240V AC & 24V to 220 V DC |
| Operating
Voltage Range |
- 10% to + 10% of rated voltage |
| Rated
Frequency |
50 Hz ±5% |
| Control
Output |
2c/o rated for 5A@ 250V AC/28V DC, Resistive load |
| Time Range |
3 Sec to 30 Sec |
| Setting
Accuracy |
± 10% max.w.r.t. Full Scale ±100 msecs |
| Repeat
Accuracy |
± 1% maximum ±100 msecs |
| Recovery
Time |
100 msecs. minimum |
| Rated
Frequency of operation |
1800 ± 5% operations per hour maximum |
| Variation
due to voltage change |
±2% max.±100 msecs |
| Variation
due to temp.change |
±5% max.±100 msecs |
| Variation
due to frequency change |
±2% max.±100 msecs |
| Ambient
temperature |
Operating: -10° C to + 55° C
Storage : - 25° C to + 80° C |
| Humidity |
Max. 85% RH @ 40° C |
| Service
Life |
106 operations minimum(under no load) |
| Electrical
Life |
105 operations minimum(under full load) |
| Electrical Connections |
11 pin plug-in-type |
| Dimensions |
48 x 48x 94mm [W x H x D] |
| Allowable Ripple(for DC Supply) |
3% Max. |
| Power
Consumption |
AC approx 3VA/1W DC Approx.2W |
| Insulation
Resistance |
>100M ohms @ 500V DC |
| Dielectric Strength |
01) 1.5KV AC(rms),50Hz for 1minute.(Between INPUT terminals & enclosure)
02) 1.5KV AC(rms), 50Hz for 1 minute.(between relay contact terminals & enclosure)
03) 1.5 KV AC(rms), 50 Hz for 1minute.(Between INPUT terminals & relay contact terminals)
04) 1.0Kv AC(rms), 50Hz for 10-30 sec. (Between non-continuous contacts of the relay) |
| Enclosure (Series) |
H1D Series |
| Panel
cutout |
45mm X 45mm |
| Approval |
CSA (FILE NO : LR 105610) |