| Model : H1D1-X(CSA) |
| Operating
Voltage Range |
-10% to +10% of rated voltage |
| Rated
Frequency |
50 Hz ±5% |
| Control
Output |
2 c/o rated for 5A@ 250V AC/28V DC, Resistive load |
| Setting
Accuracy |
± 10% max.w.r.t. Full Scale ±100 msecs |
| Repeat
Accuracy |
± 1% maximum ±100 msecs |
| Recovery
Time |
100 msecs. minimum |
| Rated
Frequency of operation |
1800 ±5% operations per hour max. |
| Variation
due to voltage change |
±2% max.±100 msecs |
| Variation
due to temp.change |
±5% max.±100 msecs |
| Variation
due to frequency change |
±2% max.±100 msecs |
| Ambient
temperature |
Operating:- 10° C to + 55° C
Storage : - 25° C to + 80° C |
| Humidity |
Max. 85% RH @ 40° C |
| Service
Life |
106 operations minimum(under no load) |
| Electrical
Life |
105 operations minimum(under full load) |
| Connections |
11 pin plug-in-type |
| Dimensions |
48 x 48x 94mm [W x H x D] |
| Power
Consumption |
AC approx. 3VA/1W
DC approx.2W |
| Insulation
Resistance |
>100M ohms @ 500V DC |
| Range
Selection |
3s,6s,30s,60s,3m,6m,30m,60m |
| Descriptive Strength |
01) 1.5KV AC(rms),50Hz for 1minute.(Between INPUT terminals & Enclouser)
02) 1.5KV AC(rms), 50Hz for 1 minute.(between relay contact terminals & enclosure)
03) 1.5 KV AC(rms), 50 Hz for 1minute.(Between INPUT terminals & relay contact terminals)
04) 1.0KV AC(rms), 50Hz for 10-30 Sec.(Between non-continuos contacts of the relay) |
| Allowable
Ripple |
3% Maximum (for DC supply) |
| Approval |
CSA (FILE NO : LR 105610) |